ABB Temperature Transmitter TTH300 Module HART 4-20mA Output The two-channel temperature transmitter TTH300 with HART, PROFIBUS
PA or FOUNDATION Fieldbus in two-wire technology has extensive
functions and diagnostic options for all applications. For the new
TTH300 HART, these have been expanded once again and the
user-friendliness has been further improved. The TTH300 is provided for the highest requirements of temperature
measurement with two sensor inputs. This supports sensor redundancy
and sensor drift monitoring. The transmitter follows NAMUR
Recommendations such as NE 89 and NE 107. As an option, an LCD
indicator with operating buttons can be connected. The TTH300 HART can be configured with ABB-tools such as Field
Information Manager (FIM), with DAT200 (Asset Vision Basic) via
DTM, with a Handheld via EDD, or with any standard tool using
FDI-/FDT-Technology. Transmitter with PROFIBUS PA can be configured via GSD file, EDD or
DTM, with FOUNDATION Fieldbus via EDD/CF. Data- Two universal sensor inputs, each for RTD, thermocouple, Ω, mV
- Functional safety SIL 2 / SIL 3 in accordance with IEC 61508 (HART
variant)
- Various sensor error-calibration possibilities
– One point, two point, Callendar-van-Dusen, freestyle
characteristics with 32 supporting points - Sensor backup / automatic sensor redundancy switching (2 x Pt100
3-wire connection and further sensor combinations)
- Redundancy behavior configurable for increased availability,
increased safety or increased accuracy (HART variant)
- Output signal
– 4 to 20 mA, HART 5 and HART 7 (switchable) – PROFIBUS PA 3.01 – FOUNDATION Fieldbus ITK 5.x - Accuracy 0.1 %, long-term stability 0.05 % per year
- Wire break / corrosion monitoring in accordance with NE 89
- Device status signaling and freely configurable diagnostic
categorization with diagnostic history according to NE 107 (HART
variant)
- Event monitor for logging critical events (HART variant)
- Configuration monitor for configuration changes (HART variant)
- Turnable LCD indicator with operating buttons (option)
- Approvals for explosion protection
– ATEX, IECEx, zone 0 – FM / CSA – EAC, EAC-Ex – NEPSI
item | value | Place of Origin | Original | Brand Name | Original | Model Number | TTH300-S1H | condition | new&original | Shipping Method | Fedex/DHL/UPS/EMS/Others | Lead Time | 1-5 days |
|