| System function |
1.Use DC or high-voltage pulse to make the cable fault point flash
over and discharge
2.Use the traveling wave reflection principle to make a rough
measurement of all types of cable main insulation faults
3.Use the acoustic-magnetic synchronization method to make a
precise measurement of all types of cable main insulation fault
|
| I,High voltage surge generator XHHV535-4T |
| Output mode | DC, Single, Cycle |
| Output voltage | 0-8kV/0-16kV/0-32kV, three voltage switchable |
| Built-in capacitor | 64μF/16μF/4μF |
| Discharge energy | 2048J |
| Impact power | 2000VA |
| Impulse rate | Automatic impact for about 6 seconds, manual impact for any control
time |
| Surge voltage levels switch | Manual |
| Voltage adjustment type | Continuous |
| Indication | High-voltage side voltage metering, indication of output voltage
and current in real time |
| Operating modes switch | Manual |
| Continuous output current | 60mA |
| Safe protection | With zero start protection function, safe and reliable |
| Discharge | Unique high-voltage measurement design, in the stop state, it will
automatically discharge the internal capacitance of the device |
| Working power | AC 220V±15% ,50Hz±2Hz |
| DC withstand voltage testing | Output voltage adjustable and indication range 0-35Kv, output
current indication range 0-20A |
| Burn current | Fault conditioning (burning) with current up to 60 mA @ 32 kV |
| Safety | Over-voltage, Over-current, Overheating protection. Automatic discharge after operation |
| Protection rating | Not lower than IP54 |
| Dimensions(mm) | 534L×444W×805H mm |
| Total weight | Not more than 120kg |
| II,TDR cable fault locator XHGG502A |
| Test method | Low voltage pulse, Impulse current, Impulse voltage, ARC multipls
pulse |
| Sampling rate | 1MHz~400MHz |
| Pulse output | Unipolar |
| Pulse Amplitude | 300V |
| Pulse width | 0.15μS/0.30μS /0.60μS/1.20μS/2.4μS/5.0μS/7.5μS/10μS |
| Measurement scope | ≥120km |
| Measurement range | 100m/300m/500m/1km/3km/5km/10km/25km/50km/100km |
| Minimum resolution | 0.07m |
| Measurement error | ≤±(0.5%×L+1m),L is cable length |
| Signal gain | 0…100%,adjustable |
| Propagation speed | 10…999.9m/µs |
| Output Impedance | Automatic match |
| Trigger | Automatic continute
|
| Working conditions | temperature -25℃~+65℃, relative humidity 85%, atmospheric pressure
750±30mmHg |
| III,Cable fault pinpointer XHDD503C |
| Fixed-point mode | Standard mode, enhanced mode, noise reduction mode, custom mode
(ms, waveform) |
| Fixed point method | Intelligent time difference method, electromagnetic inspection
method, acoustic measurement method |
| Positioning accuracy | Fixed point: 0.1m, Path: 0.1m |
| Display | TFT ultra-bright 5-inch, 800×480 true color |
| language | Graphical language is more intuitive |
| Gain | 120dB, fully automatic adjustment, also can be adjusted manually |
| Frequency range | 100~1600Hz |
| Dynamic Range | 0~112dB(16 gears) |
| Synchronous trigger | Acoustic fully automatic synchronous trigger; magnetic field fully
automatic synchronous trigger |
| Detection range | 0.00~99.99ms,75mV~75V |
| Probe | Automatic mute, fully digital metal intelligent probe |
| Headphone | 600Ω military-grade strong noise reduction and anti-interference
technology |
| Working power | 4*18650 Standard lithium battery |
| Working hours | More than 8 hours |
| Ambient temperature | -25~65℃; relative humidity: ≤90% |
| Weight | Host 0.6kg; Sensor 1.4kg |
| Waterproof grade | IP65 |
| IV,Cable path comprehensive tester |
| Transmitter |
|
| Output frequency | Low frequency(815Hz), intermediate frequency(8kHz), high
frequency(33kHz), radio frequency(83kHz) |
| Output power | 10W,Four output levels: low, medium, high, full |
| Output voltage | 150Vpp |
| Output mode | Direct connection method, coupling method, induction method |
| Display | Output mode, frequency, output power, loop resistance, loop
current, battery remaining capacity, dangerous voltage alarm, etc. |
| Coupling clamp | Coupling inner diameter Φ150mm |
| Receiver |
|
| Working mode | Tracing, identification, Step voltage |
| Receiving frequency | Low frequency(815Hz), intermediate frequency(8kHz), high
frequency(33kHz), radio frequency(83kHz) |
| Display | Depth, current, frequency, mode, gain, signal strength, date, time,
etc. |
| Detection depth | ≥10m |
| V Test cables |
| (Note: Due to the existence of 35kV high voltage, special high
voltage cables are made and should be kept away from the site
during operation.) |
| High voltage output cable | core wire 2.5mm2 red, withstand voltage 50kV DC, with shielding
layer, outer diameter 14mm, length 10 meters, including
installation of large spool. |
| Ground cable | grounding 3-column - main core 16mm2 transparent color, branch
2.5mm2, length 10 meters. Including installation of small spool. |