model | 3H 30 KL |
capacity | 30000VA / 24000W |
enter |
Voltage range | 190-520VAC (3 phase) 50% load |
305-478VAC (3 phase) 100% load |
Frequency range | 46Hz ~ 54 Hz @ 50Hz system |
56Hz ~ 64 Hz @ 60Hz system |
Phase | Three-phase grounding |
Power Factor | ≧ 0.99 at 100% load |
Output |
Phase | Single phase (live wire + neutral wire + ground wire) |
Output voltage | 208/220/230/240VAC |
AC Voltage Range | ± 1% |
Frequency range (synchronization range) | 46Hz ~ 54 Hz @ 50Hz system |
56Hz ~ 64 Hz @ 60Hz system |
Frequency range (battery mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Overload | Mains mode | 100%~110%: 10 minutes; 110%~130%: 1 minute; >130%: 1 second |
Overload, switch to bypass mode |
Battery Mode | 100%~110%: 30 seconds; 110%~130%: 10 seconds; >130%: 1 second |
Overload, switch to bypass mode |
Current peak ratio | 3:1 max |
Harmonic distortion | ≦ 2 % @ 100% linear load; ≦ 5 % @ 100% non-linear load |
Switching time | Online ← →Battery | 0 ms |
Inverter← → Bypass | 0 ms |
Inverter ← → ECO | <10 ms |
Output power factor | 0.8 |
Parallel capacity | Supports up to 3 units in parallel (not supported by the commonly
sold models) |
Waveform | Pure sine wave |
Inverter mode | IGBT |
Control method | MCU+DSP |
efficiency |
AC Mode | > 90 % |
Battery Mode | > 8 8 % |
Long-lasting machine (number of battery cells is factory
adjustable) | model | Depends on battery configuration |
number | 16 - 20 |
Charging current (maximum) | 12.0A ±10% |
Charging voltage | 273 VDC ± 1% (based on 20 batteries) |
Display instructions |
LCD | Visually display load size, battery capacity, AC mode, battery
mode, bypass mode, fault indication, etc. through images |
The output voltage, frequency, bypass enable, ECO function,
charging current, discharge time, etc. can be adjusted through the
screen display menu |
Appearance |
Long extension machine | Dimensions, depth x width x height (mm) | 815 x 300 x 1000 |
Net weight(kgs) | 64 |
Environmental conditions |
Operating temperature | 0 ~ 40°C (Battery life will be shortened in environments > 25°C) |
Operating humidity | <95 % without condensation |
Operating altitude | <1000m |
noise | Less than 65dB @ 1 Meter |
manage |
Intelligent RS-232 or USB | Supports Windows® 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC |
Optional SNMP | Supports power management via SNMP manager and web browser |