Pepperl Fuchs Inductive sensor NCB5-18GM40-N0 Polarity reversal protected
|
Pepperl Fuchs Inductive sensor NCB5-18GM40-N0 5 mm flush Usable up to SIL 2 acc. to IEC 61508 NAMUR output Stainless steel housing Polarity reversal protected General specifications Switching function Normally closed (NC) Output type NAMUR Rated operating distance 5 mm Installation flush Assured operating distance 0 ... 4.05 mm Actual operating distance 4.5 ... 5.5 mm typ. 5 mm Reduction factor rAl 0.35 Reduction factor rCu 0.3 Reduction factor r304 0.74 Output type 2-wire Nominal ratings Nominal voltage 8.2 V (Ri approx. 1 kΩ) Switching frequency 0 ... 400 Hz Hysteresis 1 ... 15 % typ. 5 % Reverse polarity protection reverse polarity protected Short-circuit protection yes Current consumption Measuring plate not detected min. 3 mA Measuring plate detected ≤ 1 mA Switching state indicator all direction LED, yellow Functional safety related parameters Safety Integrity Level (SIL) SIL 2 MTTFd 2040 a Mission Time (TM) 20 a Diagnostic Coverage (DC) 0 % Compliance with standards and directives Standard conformity NAMUR EN 60947-5-6:2000 IEC 60947-5-6:1999 Electromagnetic compatibility NE 21:2007 Standards EN IEC 60947-5-2 |
![]() |
P&F/TB-C3-DO32-AKB-Y188682 NAMUR switching amplifier Current Rating 4-8A per contact depends on wiring |
![]() |
LED Pepperl Fuchs Safety Barrier Vt18 8 H 120 M 40a 65b 118 128 Diffuse Mode Sensor Flashing |
![]() |
2000mm Universal Power Rail UPR 03 PEPPERL FUCHS Eliminates Daisy Chains |
![]() |
KCD2-STC-Ex1.2O Terminal Blocks l P&F Pepper Fuchs Safety BarrierTransmitter Power Supply |
![]() |
230VAC Rotation Speed Monitor KFA6-DWB-Ex1.D Supply PEPPERL FUCHS |
![]() |
0 - 20V Pepperl Fuchs Safety Barrier Voltage Repeater KFD2-VR4-Ex1.26 |