3 Pole MCB Perkins Diesel Generator , 404C-22G1 HS , 380 - 415V
|
|
1. Standby power: 24 kw 2.Engine Make & Model: Perkins 404C-22G1 HS 3.Alternator Model: LL1012N 4.Fuel Tank Capacity: litres (US gal):45 (11.9) 5.Cooling Method: Water Governing 6.Compression Ratio: 23.3:1 7.Displacement: l (cu.in) 2.2 (135.2) 8.Bore/Stroke: mm (in) 84.0 (3.3)/100.0 (3.9) 9.Moment of Inertia: kg m² (lb. in²) 3.20 (10935) 10.Weights: kg (lb) : 446 (983) 3 Pole MCB Perkins Diesel Generator , 404C-22G1 HS
Ratings at 0.8 power factor.
PH30E2
Engine Technical Data
Physical Data
Manufacturer: Perkins Model: 404C-22G1 HS No. of Cylinders/Alignment: 4 / In Line Cycle: 4 Stroke Induction: Naturally Aspirated Cooling Method: Water Governing Type: Mechanical Governing Class: ISO 8528 G2 Compression Ratio: 23.3:1 Displacement: l (cu.in) 2.2 (135.2) Bore/Stroke: mm (in) 84.0 (3.3)/100.0 (3.9) Moment of Inertia: kg m² (lb. in²) 3.20 (10935) Engine Electrical System: -Voltage/Ground: 12/Negative -Battery Charger Amps: 55 Weight: kg (lb) - Dry: 218 (481) - Wet: 234 (517)
Air System 50 Hz 60 Hz
Air Filter Type: Replaceable Element Combustion Air Flow: m³/min (cfm) -Standby: 2.4 (85) -Prime: - Max. Combustion Air Intake Restriction: kPa (in H2O) 6.4 (25.7) - Radiator Cooling Air Flow: m³/min (cfm) 71.0 (2507) - External Restriction to Cooling Air Flow: Pa (in H2O) 125 (0.5)
Cooling System 50 Hz 60 Hz Cooling System Capacity:l (US gal) 6.8 (1.8) - Water Pump Type: Centrifugal Heat Rejected to Water & Lube Oil: kW (Btu/min) -Standby: 29.3 (1666) -Prime: - Heat Radiation to Room:kW (Btu/min) -Standby: 11.9 (677) -Prime: - Radiator Fan Load: kW (hp) 1.2 (1.7) Cooling system designed to operate in ambient conditions up to 50°C (122°F).
Performance 50 Hz 60 Hz
Engine Speed: RPM 3000 - Gross Engine Power: kW (hp) -Standby: 31.9 (43.0) -Prime: - BMEP: kPa (psi) -Standby: 1151.0 (167.0) - -Prime: - - Regenerative Power: kW 19.0
LubriCAT-parts-partsion System
Oil Filter Type: Spin-On, Full Flow Total Oil Capacity l (US gal): 10.6 (2.8) Oil Pan l (US gal): 8.9 (2.4) Oil Type: AP1CH4 15W-40 Cooling Method: Water
Fuel System
Fuel Filter Type: Replaceable Element Recommended Fuel: Class A2 Diesel Fuel Consumption: l/hr (US gal/hr) 110% 100% 75% 50% Load Load Load Load
PH30E2
50 Hz 8.9 (2.4) 7.1 (1.9) 5.6 (1.5) 60 Hz - - -
(based on diesel fuel with a specific gravity of 0.85 and conforming to BS2869, Class A2)
Exhaust System 50 Hz 60 Hz
Silencer Type: Level 1 Silencer Model & Qty: MXC0996 (1) Pressure Drop Across Silencer System: kPa (in Hg) 5.03 (1.485) - Silencer Noise Reduction Level: dB - Max. Allowable Back Pressure: kPa (in. Hg) 10.2 (3.0) - Exhaust Gas Flow: m³/min (cfm) -Standby: 7.6 (268) -Prime: - Exhaust Gas Temperature: °C (°F) m³/min (cfm) -Standby: 475 (887) -Prime: PH30E2
Alternator Performance Data
Reactances shown are applicable to prime ratings
** With optional Permanent Magnet generator or AREP excitation.
Alternator Technical Data
PH30E2
Technical Data
3 Phase Ratings and Performance at 50 Hz, 3000 RPM 3 Phase Ratings and Performance at 60 Hz,
Definitions Standby Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).
Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.
Standard Reference Conditions Note: Standard reference conditions 27°C (80°F) Air Inlet Temp, 152.4m (500ft) A.S.L. 60% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.
Weights and Dimensions
Weights: kg (lb) Dimensions: mm (in)
General Data
Documents
A full set of operation and maintenance manuals, circuit wiring diagrams, and commissioning/fault finding instruction leaflets.
Generating Set Standards
The equipment meets the following standards: BS5000, ISO 8528, ISO 3046, IEC 60034, VDE 0530, NEMA MG-1.22.
FG Wilson is a fully accredited ISO 9001 company.
Warranty
All equipment carries full manufacturer's warranty. Extended warranty terms available.
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Product Tags: standby diesel generator diesel generators sets | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
60KW Perkins Silent Portable Diesel Generator 3kva To 3000kva |
|
50KW Perkins 3 Phase 4 Cylinder Diesel Generator For Fishing Grounds |
|
40KW Trailer Type Perkins Diesel Generator For Transportation Farmland |
|
Perkins 30KW Soundless Diesel Generator For Home Backup Emergency |
|
100KW Water Cooled 4 Stroke Perkins Diesel Generator With Heavy Duty Radiator |
|
Mine Power Generation Noise 95dB Perkins Diesel Generator Sold For Factory |